Square counter flow cooling tower


A square counter flow fiberglass cooling tower with a single water volume of 100-4000m3/h. It has the characteristics of good thermal performance, low power consumption, good overall tower stability, beautiful appearance, low noise, short construction and installation period, and low cost, and is widely used in enterprises such as petroleum, chemical, metallurgical, and power generation.
  • DESCRIPTION
    • Commodity name: Square counter flow cooling tower
    • Commodity ID: Square counter flow cooling towe

    A square counter flow fiberglass cooling tower with a single water volume of 100-4000m3/h. It has the characteristics of good thermal performance, low power consumption, good overall tower stability, beautiful appearance, low noise, short construction and installation period, and low cost, and is widely used in enterprises such as petroleum, chemical, metallurgical, and power generation.

    Features:

    1. Standard design conditions: dry bulb temperature 31.5 °C, wet bulb temperature 28 °C, atmospheric pressure 99400Pa, inlet water temperature 42 °C, outlet water temperature 32 °C.

    2. The special packing of the inclined trapezoidal wave square tower is selected, which has excellent thermal performance and low ventilation resistance, so that this kind of cooling tower can achieve the design purpose of compact structure and small footprint.

    3. The airfoil type fasting structure is used for large diameter, large area, low speed and low dynamic pressure FRP fan blades, and the use of this kind of cooling tower has the remarkable characteristics of energy saving and low noise.

    4. The ultra-low noise cooling tower is equipped with a high-efficiency noise reduction device at the air inlet and outlet and in the rain area, so that the effective noise reduction of the cooling tower of the same level can reach 5dB (A).

    5. It can be combined in various forms in parallel, which is more suitable for the use of circulating cooling water system with large water volume.

    6. The fixed water distribution system is adopted, and the ABS multi-layer flow low-pressure water sprinkler is selected, which has uniform water distribution, long service life, and low water distribution pressure head, which is conducive to saving the water distribution power of the system.

    7. BO-160/45 asymmetrical water collector device is set on the water distribution pipe, which has excellent water collection effect and reduces the floating water loss of the cooling tower to less than 0.01%.

    8. The tower frame can be made of Q-235 profiles, 304 stainless steel profiles and FRP profiles, and the "304/FRP" frame can be used in an acidic environment with a circulating water pH as low as 1.0.

    9. The cooling tower frame with a water volume of 800m3/h can be made of reinforced concrete, although the frame has a slightly longer construction period and a higher one-time investment, it has a long service life and low maintenance costs, and the user can choose according to the actual situation.

    10. If the turbidity of circulating water is higher than 50ppm for a long time, or impurities such as oily pollution, it is necessary to choose PVC grid filler or 304 stainless steel baffle plate drip filling according to water quality conditions, and the turbidity of the circulating water suitable for the filler can be extended to 450ppm.

    11. The structure is stable, and the maintenance platform is set at the top of the tower, which is more convenient for maintenance and overhaul.

     

    The main parameters of the low temperature drop DFN series square counter-current FRP cooling tower

    Model

    T=28°C cooling water (m3/h)

    T = 27°C cooling water

    (m3/h)

    Main dimensions (mm)

    Air

    (m3/h)

    Fans

    diameter

    (mm)

    Motor

    Power(KW)

    Water

    pressure

    104Pa

    Noise dB(A)

    equivalent

    diameter

    Dm

    △t=5℃

    △t=5℃

    △t=5℃

    △t=5℃

    Overall height

    Width B

    Dm  

    10m  

    16m  

    DFNL-100

    100

    74.4

    118.7

    86.0

    3830

    2600

    62000

    1800

    3.0/1.5

    6.2

    59.0

    52

    47.0

    3.02

    DFNDP-100

    4390

    DFNGP-100

    4690

    DFNL-150

    150

    109.8

    175.1

    126.9

    4050

    3000

    84000

    2400

    4.0/2.0

    6.3

    60.5

    54

    50.6

    3.47

    DFNDP-150

    4670

    DFNGP-150

    4970

    DFNL-200

    200

    148.9

    237.4

    172.1

    4340

    3600

    115000

    2800

    5.5/2.7

    6.5

    62.0

    55.6

    52.3

    4.15

    DFNDP-200

    4960

    DFNGP-200

    5260

    DFNL-300

    300

    224.9

    350.6

    258.3

    5010

    4300

    158600

    3400

    7.5/3.7

    5.8

    62.0

    57.8

    54.5

    4.94

    DFNDP-300

    5690

    DFNGP-300

    5990

    DFNL-400

    400

    299.9

    467.4

    344.4

    5300

    4800

    213000

    3800

    11/5.5

    6.0

    62.5

    58.8

    55.7

    5.51

    DFNDP-400

    6040

    DFNGP-400

    6340

    Illustrate:

    1. The wet-bulb temperature listed in the table is τ=28°C, τ=27°C; Δt=5°C t1=37°C, t2=32°C; Δt=8°C, t1=40°C, t2=32°C.

    2. The noise value in the table is the value of the low-speed operation of the motor at night and the dripping sound-absorbing pad, and the dripping sound-absorbing pad will be 5dB (A) higher than the value in the table without the dripping sound-absorbing pad.

     

    The main parameters of the low temperature drop DFN series square counter-current FRP cooling tower

    Model

    T=28°C cooling water (m3/h)

    T = 27°C cooling water

    (m3/h)

    Main dimensions (mm)

    Air

    (m3/h)

    Fans

    diameter

    (mm)

    Motor

    Power(KW)

    Water

    pressure

    104Pa

    Noise dB(A)

    equivalent

    diameter

    Dm

    △t=5℃

    △t=5℃

    △t=5℃

    △t=5℃

    Overall height

    Width B

    Dm  

    10m  

    16m  

    DFNL-500

    500

    374.9

    548.3

    430.4

    5900

    5300

    265000

    3800

    15/7.5

    6.4

    62.5

    59.3

    56.2

    6.08

    DFNDP-500

    6700

    DFNGP-500

    7000

    DFNL-600

    600

    448.5

    698.9

    514.9

    6140

    6000

    317500

    4200

     

    15/7.5

     

    6.5

    62.5

    60.5

    57.4

    6.88

    DFNDP-600

    6980

    DFNGP-600

    7280

    DFNL-750

    750

    561.7

    875.3

    644.9

    6440

    6800

    400000

    4200

    22/11

    6.8

    63.0

    61.4

    58.4

    7.79

    DFNDP-750

    7290

    DFNGP-750

    7590

    DFNL-900

    900

    673.4

    1049.5

    773.2

    6950

    7300

    490000

    4700

    30/15

    7.0

    63.8

    62.9

    60.0

    8.36

    DFNDP-900

    7900

    DFNGP-900

    8200

    DFNL-1050

    1050

    786.6

    1225.9

    903.1

    7150

    7800

    556000

    4700

    30/15

    7.0

    64.6

    63.1

    53.9

    8.93

    DFNDP-1050

    8100

    DFNGP-1050

    8400

    Illustrate:

    1. The wet-bulb temperature listed in the table is τ=28°C, τ=27°C; Δt=5°C t1=37°C, t2=32°C; Δt=8°C, t1=40°C, t2=32°C.

    2. The noise value in the table is the value of the low-speed operation of the motor at night and the dripping sound-absorbing pad, and the dripping sound-absorbing pad will be 5dB (A) higher than the value in the table without the dripping sound-absorbing pad.

     

    The main parameters of medium and high temperature industrial GFN series square counterflow FRP cooling tower

    Model

    T=28°C cooling water (m3/h)

    T=27°C cooling water (m3/h)

    Main dimensions (mm)

    Air

    (m3/h)

    Fans

    diameter

    (mm)

    Motor

    Power(KW)

    Water

    pressure

    104Pa

    Noise dB(A)

    equivalent

    diameter

    Dm

    △t=10℃

    △t=20℃

    △t=25℃

    △t=10℃

    △t=20℃

    △t=25℃

    Overall height

    Width B

    GFNL-75

    75

    66.9

    65.8

    86.3

    73.6

    71.8

    3830

    2600

    68000

    1800

    3.0/1.5

    6.2

    59.0

    3.02

    GFNDP-75

    4390

    GFNGP-75

    4690

    GFNL-100

    100

    89.2

    87.7

    115

    98.1

    95.7

    4050

    3000

    88000

    2400

    4.0/2.0

    6.3

    60.5

    3.47

    GFNDP-100

    4670

    GFNGP-100

    4970

    GFNL-150

    150

    137.4

    136.2

    172.2

    150.2

    147.7

    4840

    3600

    121000

    2800

    5.5/2.7

    6.5

    62.0

    4.15

    GFNDP-150

    5460

    GFNGP-150

    5760

    GFNL-200

    200

    182.8

    181.3

    229.1

    199.8

    196.5

    5010

    4300

    161000

    3400

    7.5/3.7

    5.8

    62.0

    4.94

    GFNDP-200

    5690

    GFNGP-200

    5990

    GFNL-250

    250

    228.2

    226.3

    286

    249.4

    245.3

    5300

    4800

    201000

    3800

    11/5.5

    6.0

    62.5

    5.51

    GFNDP-250

    6040

    GFNGP-250

    6340

    说明:

    1表中所列为湿球温度 τ=28℃ , τ=27℃工况下; Δt=5℃ 的t1=37℃,t2=32℃; Δt=8℃时t1=40℃,t2=32℃的冷却水量。

    2. The noise value in the table is the value of the low-speed operation of the motor at night and the dripping sound-absorbing pad, and the dripping sound-absorbing pad will be 5dB (A) higher than the value in the table without the dripping sound-absorbing pad.

     

    The main parameters of medium and high temperature industrial GFN series square counterflow FRP cooling tower

    Model

    T=28°C cooling water (m3/h)

    T=27°C cooling water (m3/h)

    Main dimensions (mm)

    Air

    (m3/h)

    Fans

    diameter

    (mm)

    Motor

    Power(KW)

    Water

    pressure

    104Pa

    Noise dB(A)

    equivalent

    diameter

    Dm

    △t=10℃

    △t=20℃

    △t=25℃

    △t=10℃

    △t=20℃

    △t=25℃

    Overall height

    Width B

    GFNL-300

    300

    273.6

    271.3

    342.9

    299.1

    294.1

    5900

    5300

    241000

    3800

    11/5.5

    6.4

    62.5

    6.08

    GFNDP-300

    6700

    GFNGP-300

    7000

    GFNL-400

    400

    364.6

    361.4

    456.7

    398.3

    391.8

    6140

    6000

    312000

    4200

    15/7.5

    6.5

    62.5

    6.88

    GFNDP-400

    6980

    GFNGP-400

    7280

    GFNL-500

    500

    455.2

    451.5

    570.5

    497.6

    489.4

    6440

    6800

    401000

    4200

    22/11

    6.8

    63.0

    7.79

    GFNDP-500

    7290

    GFNGP-500

    7590

    GFNL-600

    600

    546

    541.5

    684.3

    596.9

    589.1

    6950

    7300

    481000

    4700

    30/15

    7.0

    63.8

    8.36

    GFNDP-600

    7900

    GFNGP-600

    8200

    GFNL-700

    700

    638

    632.7

    799.6

    697.4

    685.9

    7150

    7800

    560000

    4700

    30/15

    7.0

    64.6

    8.93

    GFNDP-700

    8100

    GFNGP-700

    8400

    Illustrate:

    1. The wet-bulb temperature listed in the table is τ=28°C, τ=27°C; Δt=5°C t1=37°C, t2=32°C; Δt=8°C, t1=40°C, t2=32°C.

    2. The noise value in the table is the value of the low-speed operation of the motor at night and the dripping sound-absorbing pad, and the dripping sound-absorbing pad will be 5dB (A) higher than the value in the table without the dripping sound-absorbing pad.

     